This is an old revision of the document!


IH: Electrical System - Sub-02A

Bench Testing a Generator

Article by sifty of the XLFORUM 1)

Some simple diagnostic tests can be done with a multimeter.
Note, these tests should be performed after the initial visual inspection and cleaning as outlined in the service manuals.
And so are based on testing the unit out of the bike.
The results of these tests should determine if anything is seriously wrong.
But will not identify an intermittent generator fault,
(these can be hard to diagnose, and probably need testing on the bike so the genny can be driven at varying revs).

  • Generators are fairly simple, they consist of;
    • Field windings are designated “F” (attached to the case).
    • Armature windings are designated as “A” (wound around the rotating shaft).
    • And spring loaded brushes which connect to the commutator section of the armature.
  • Most generators will be the 65 or 65A type.
  • You can identify the “A” terminal (if not marked) by seeing which one goes to both a field winding and one of the brushes.
  • Note this brush must be insulated from the brush plate, while the other brush is not as it is the negative part of the 12V circuit.
    So is directly connected to ground.
  • Generally if the windings test out ok, the generator should operate correctly;
    • There are no short circuits.
    • And the commutator, brushes and bearings are clean and in good order.



This website uses cookies for visitor traffic analysis. By using the website, you agree with storing the cookies on your computer.More information